How to Size a Home Battery for a House
Sizing is arithmetic, not guesswork. Add the energy your essential loads draw in a day, add system losses, then choose the smallest pack that covers the backup window you actually need.
Step 1 — Build a load list, not a guess
Start from the appliances that must keep running during an outage. For each one write down its rated watts and the hours it runs per day. Compressor loads such as fridges and pumps cycle on and off, so count running hours rather than 24.
| Load | Rated power | Hours / day | Energy / day |
|---|---|---|---|
| Fridge–freezer | 150 W | 8.0 h | 1.20 kWh |
| LED lights ×10 | 90 W | 5.0 h | 0.45 kWh |
| TV + decoder | 120 W | 4.0 h | 0.48 kWh |
| Router / ONT | 15 W | 24.0 h | 0.36 kWh |
| Phones, laptops | 60 W | 3.0 h | 0.18 kWh |
| Water pump (0.75 HP) | 750 W | 0.5 h | 0.38 kWh |
| Total essential load | 3.05 kWh |
Keep a second column for “nice to have” loads — air conditioning, water heater, EV charging. They are usually fifteen to thirty times the essential load and should decide the size only if the customer is willing to pay for them.
Step 2 — Convert daily energy into pack size
A 5.12 kWh LiFePO₄ pack does not give you 5.12 kWh at the socket. Two losses apply: depth of discharge (how far you can empty it without shortening life) and round-trip efficiency (energy lost in charging and inverting).
LiFePO₄: DoD 0.90 × efficiency 0.92 = 0.83 usable factor
Using the table above, one day of backup for 3.05 kWh/day needs 3.05 ÷ 0.83 = 3.7 kWh — a 5.12 kWh pack covers it with margin. Two days of autonomy needs 7.3 kWh, which points to the 10.24 kWh model.
Step 3 — Check the backup time your customer expects
| Pack (nominal) | Usable | at 500 W | at 1 kW | at 2 kW |
|---|---|---|---|---|
| 5.12 kWh | 4.2 kWh | 8.4 h | 4.2 h | 2.1 h |
| 10.24 kWh | 8.5 kWh | 17.0 h | 8.5 h | 4.3 h |
| 15.36 kWh | 12.8 kWh | 25.6 h | 12.8 h | 6.4 h |
| 16 kWh | 13.3 kWh | 26.6 h | 13.3 h | 6.7 h |
Three sizing mistakes we see every week
- Sizing on the whole electricity bill. A household using 20 kWh/day may need only 4 kWh of backup, because the air conditioner and water heater are not essential. Size the critical circuits first.
- Ignoring surge. A 3 kW inverter that is perfect for the energy figure may trip on a 1.5 HP pump. Check motor start current before quoting.
- Oversizing a grid-tied system. When the goal is evening self-consumption rather than outage cover, the right size is the evening share of PV production, not the daily total. A pack that is too large never reaches a full cycle and takes years longer to pay back.
Once the capacity is fixed, confirm the voltage and communication protocol against the inverter — that is the subject of our inverter and BMS matching guide.
Talk to an engineer
Send your load list, inverter model or project quantity and we answer with a concrete configuration — not a brochure.